Inspection History: FRAMING
Permit Number - T98CM03892
Inspection Description - FRAMING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/1998 | FRAMING | Correction Required | ADDTL COMMS - SHEAR WALL STUDS ON 16 CENTER AT INT. KITCHEN WALL . CHECK AT SHEETROCK NAILING | |
10/28/1998 | FRAMING | Correction Required | ADDTL COMMS - 1. STRAP GARAGE/ HOUSE WALL AT TOP PLATE WERE DRYER DUCT GOES THROUGH. 2. INSTALL BANG PLATES EAST GARAGE WALL TOP PLATES FOR PROTECTION OF WIRES. 3. TRUSSES BEARING ON INTERIOR PARTITION WALL PROVIDE ADEQUATE CLEARANCE FOR REQUIRED DEFLECTION. 4. COMPLETE DUCT INSTALLATION L.R. 5. #4 SHEAR WALL REQUIRED 1/2 A.B. 48 O.C. (KITCHEN/ LR). 6. ADD STUD AT MB SHELVES AREA END OF SHEAR. 7. PROVIDE COMPLETE APPROVED SET OF TRUSS DRAWINGS. 8. REAR OPENING TO PATIO NOT TO PLAN? 9. STOPPED INSPECTION. | |
10/28/1998 | FRAMING | Denied | DENIED |