Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T98CM03883
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
02/17/2000 | PLUMBING - FINAL | Correction Required | ADDTL COMMS - NOTE: STOPPED INSPECTION. WE CANNOT GAS TAG OR RELEASE GAS OR FINAL ELECTRIC UNTIL THE HOUSE IS COMPLETE AND READY TO OCCUPY AND ALL REQUIRED GRADING AND SIDEWALKS ARE COMPLETE. NOT ON CUSTOMERS COPY. HOUSE CIRCUITS ARE POWERED UP FROM SOMWHERE OTHER THAN METER. GARAGE 5/8 X CEILING HAS 2 EACH 4-1/2 DIAMETER AND 5 EACH 2-5/8 PENETRATIONS FOR DRAIN/WASTE LINES OF ABS. 1. WATER HEATER VENT MUST EXTEND A MINIMUM OF 12 ABOVE PARAPET WALL. 2. ROOF FURNACE/AC CONDENSATE CANNOT BE CONNECTED TO DRAIN VENT BY DRILLING A HOLE. PROVIDE APPROVED CONNECTION. 3. OUTSIDE ELECTRIC FIXTURES ARE NOT INSTALLED. 4. LABEL SERVICE PANEL. 5. WATER HEATER REQUIRES 100 SQ.IN. COMBUSTION AIR INLET WITHIN 12 OF CEILING AND 12 OF FLOOR. 6. WATER HEATER PRESSURE AND TEMPERATURE RELIEF VALVE MUST EXHAUST OUTSIDE. 7. NO HANDRAILS ON STAIRS. 8. STAIR BOTTOM RISER IS 8-1/2. MOST RISERS ARE 6-1/2. TOP RISER IS 7-1/2. 9. NO GUARDRAILS ON THE BALCONY. | |
02/17/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* |