Permit: T98CM03868

Parcel: 120082130


Addresses:

313 W ILLINOIS ST

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
10/10/2000 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*
09/28/2000 ELECTRIC - TEMPORARY SERVICE Denied 1. THE UFER GROUND FOR THIS HOUSE APPEARS TO NOT HAVE BEEN INSPECTED OR APPROVED BY THE CITY OF TUCSON. PROVIDE PROOF OF INSPECTION OR INSTALL TWO 8 FOOT GROUND RODS AT LEAST 6 FEET APART CONNECTED TO THE SERVICE PANEL WITH A CONTINUOUS #4 GROUND WIRE.