Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 08/10/1998 |
ELECTRIC - UFER |
|
Correction Required |
ADDTL COMMS - NO PLANS OR PERMIT ON SITE, ABS PLASTIC DWV NOT PLASTIC WRAPPED, UFER CLAMP IMPROPERLY INSTALLED, COPPER CANNOT BE IN CONTACT WITH STEEL REBAR - CONNECT COPPER TO CLAMP |
| 08/07/1998 |
ELECTRIC - UFER |
|
Denied |
|