Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 06/19/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED LICENSE ELECTRICAL CONTRACTOR INVOLVED WITH DUPLEX RELOCATION AND UPGRADE OF ELECTRICAL SERVICE |
| 11/13/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/1. SQUARE D PANEL SERVICE GROUND LUG IS DESIGNED FOR ONLY ONE CONDUCTOR, TWO INSTALLED. TO INSTALL SECOND #6 THHN CONDUCTOR INSTALL A SECOND LUG OR INSTALL ON NEUTRAL X EQUIP GROUND BAR. 2. 6 X 6 CABLE TRAY NOT PROPERLY SECURED. 3. 1 1/4" CONDUIT CONNECTORS NOT PROPERLY INSTALLED TO SERVICE PANEL. 4. IN CORRECT WIRES IN CONDUITS REPLACE BLUE, YELLOW AND ZIP CORD. 5. CABLE TRENCH TOO SHALLOW CABLE MUST HAVE MINIMUM 24" COVER. 6. NORTH GROUND ROD HAS INCORRECT WIRE CLAMP GALVANIZED NOT ALLOWED. |
| 11/29/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |