Permit: T98CM03248

Parcel: 112040250


Addresses:

2823 N FORGEUS AV

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
06/27/2002 ROOF NAILING Approved IVRS - Inspection 0000*
08/01/2001 ROOF NAILING Partial Approval IVRS - Inspection 0000*/ 1) OK TO DRY IN ROOF 2) TRUSS MANUFACTERERS LETTER 12/20/00 MUST BE APPROVED AND ON FILE WITH CITY OF TUCSON PLAN CHECK
11/27/2000 ROOF NAILING Denied IVRS - Inspection 0999*/1. PLAN CALLS FOR 2 X 10 RAFTERS MAN MADE TRUSS JOISTS USED. PLAN MUST BE REVISED TO AS BUILT AND APPROVED BY PLAN CHECK. 2. TJI'S ARE WEATHER DAMAGED. REQUIRE TRUSS MANUFACTURE EVALUATION. 3. TJI HAVE ROOF SHEATHING NAILED WITH OVERSIZE NAILS. TRUSSES MUST BE EVALUATED AND APPROVED BY TRUSS MANUFACTURE. 4. YOU MUST PROVIDE TRUSS MANUFACTURES INSTALLATION INSTRUCTIONS. 5. TRUSSES MUST BE PROPERLY BLOCKED TO PREVENT TWISTING. 6. WEST TRUSS CANNOT BEAR ON 2 X 8IN FLAT.
09/10/1999 ROOF NAILING Correction Required ADDTL COMMS - OK MATER BEDROOM
09/10/1999 ROOF NAILING Partial Approval PARTIAL APPROVAL
09/08/1999 ROOF NAILING Not ready for Inspection NOT READY FOR INSPECTION
08/31/1999 ROOF NAILING Not ready for Inspection IVRS - Inspection 0000*