Inspection History Details
Permit: T98CM03129
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 08/18/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* UNIT # 2204 COMPLETE ROMEX CIRCUIT FOR RECEPT SUB FEEDS INTO SERVICE PANELS NEEDS AT LEAST 1/4" OF OWTER SHEATH PAST PENETRATION. CAULK GAPS IN BUSHINGS BEHIND SERVICE PANELS INSTALL RACEWALLS AND FIRE CAULK SUB FEED PENETRATIONS BETWEEN UNITS |