Permit: T98CM02678

Parcel: 114466640

Inspection Status: Correction Required

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T98CM02678

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/01/1998 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - 1. HEADER SCHEDULE IS ON PLAN BUT NEED INFORMATION AS TO SIZES AND IF SIZES INCREASE OR DECREASE HOW MANY SCREWS GO IN FLANGES. 2. QUESTION HAS ENGINEER OR STEEL FRAME CONSULTED WITH ROOF TRUSS DESIGNER AS TO CONCENTRATED LOADS FOR GIRDER TRUSSES AND BEAMS. 3. PLEASE EXPOSE AT LEASE FLANGE SIDE OF HEADER TO VERIFY SCREWS