Permit: T98CM02659

Parcel: 138190490


Addresses:

150 W MEDINA RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T98CM02659

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/11/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
10/20/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/1. PROVIDE BUSHING AND GROUND SCREWS TO ALL METAL BOXES. 2. MAKE UP ALL COMBINED WIRE GROUND. 3. CURRENT UFFER AT PANEL CAN NOT BE SPLICED WITH ACORN PROVIDE IRREVERISBLE CRIMP OR WEEP. (CAT) OR PROVIDE 2-8' GROUND RODS. OK TO INSTALL MECHANICAL.