Inspection Status: Approved
Inspection History: PERMIT FINALED
| Date |
Description |
Inspector |
Results |
Comments |
| 10/05/2000 |
PERMIT FINALED |
|
Approved |
IVRS - Inspection 0000* |
| 09/28/2000 |
PERMIT FINALED |
|
Denied |
1. FIRE PLACE CHIMNEY MUST BE AT LEAST 2 FEET HIGHER THAN ANY ROOF SURFACE WITHIN 10 FEET HORIZONTALLY. 2. ALUMINIUM WIRE CONNECTIONS IN ELECT SERVICE MUST HAVE ANTI CORROSIVE COMPOUND. 3. TRIM CLEAN OUTS TO GRADE. 4. TAPE W/H AND FURNACE VENT CONNECTION. 5. PLUG ALL NON USED GAS LINE. 6. BATH FANS NOT IN ALSO KITCHEN. 7. HALL BATH GFCI HOT WHEN TRIPPED LOAD AND LINE REVERSED. 8. BLOCK FP DAMPER OPEN. NEED INSULATION CERT. |