Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/06/1998 |
FRAMING |
|
Correction Required |
ADDTL COMMS - ALL METAL BOXES TO BE GROUNDED DRYER RECEP BOX NOT INSTALLED AT THIS TIME |
| 10/02/1998 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. METAL BOXES NOT GROUNDED PROPERLY USE APPROVED GREEN GROUNDING SCREW. 2. INTERIOR BEARING WALL NOT CLIPPED AT HEADERS, PLATES AND RAFTERS. 3. DUCT WORK NOT COMPLETE. 4. STRAP CARPORT HEADER. 5. SMOKE DETECTORS NOT WIRED IN SERIES. 6. DRYER OUTLET NOT IN |
| 10/02/1998 |
FRAMING |
|
Denied |
DENIED |
| 09/30/1998 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. 2X6 HEADERS AT INT BEARING DOOR OPENINGS NOT REQUIRED WERE THERE IS A BEAM ABOVE. 2. STACK STUDS IN BEARING WALL BACK BEDROOM 16 O.C. 3. H2.5 ON EVERY OTHER STUD AND CLIP HEADERS TO KING STUDS IN INT. BEARING WALL. 4. TIE ALL GROUNDS TOGETHER AND GROUND ALL METAL BOXES. 5. FIRE BLK ALL DROP CEILING AREA. 6. NEED 1 CLEARANCE FROM COMBUSTIBLES ON FLUE PIPE. 7. INSULATE DUCT WORK MECHANICAL NOT READY. 8. SMOKE DETECTORS WIRED IN SERIES. 9. O.S. OUTLETS TO BE GFI PROTECTED. 10. DRYER NEEDS 10-3W GROUND. |
| 09/30/1998 |
FRAMING |
|
Partial Approval |
PARTIAL APPROVAL |