Permit: T98CM01900

Parcel: 141201950

Inspection Status: Correction Required

Inspection History: FRAMING

Date Description Inspector Results Comments
06/12/1998 FRAMING Correction Required ADDTL COMMS - 1. SUPPORT ALL EDGES OF SHEAR WALL 7 AND NAIL ALL SUPPORTING EDGES OF TIGHT WITH FRAME. 2. H2.5 CLIPS REQUIRED AT EACH TRUSS AT SHEAR WALL 7 SEE 4/A8 ALSO STUDS TO DOUBLE TOP PLATE. 3. BLOCK DEFUSERS 3 SIDES. 4. DEAD WOOD NOT ATTACHED TO WALLS IN HALL. 5. NON BEARING WALL STUD CUT GREATER THAN 60% AT RANGE. 6. PROVIDE APPROVED REPAIR DOCUMENTS FOR THREE TRUSSES NOT ON 3 PT BEARING.
06/12/1998 FRAMING Denied DENIED
06/04/1998 FRAMING Denied DENIED