Inspection History Details
Inspection Status: Correction Required
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T98CM01884
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/1998 | EXT METAL CLIPS/EXT SHEATHING | Correction Required | ADDTL COMMS - FIRESTOP ENTRY COLUMNS AT ENTRY & AT REAR PORCH & GARAGE WINDOWS, RAMSET ALL INTERIOR BEARING WALL SILL PLATES, FINISH CLIPPING INTERIOR BEARING STUDS AT 32 O.C. & HEADERS TO KING STUDS, GAS PRESSURE TEST NEEDS TO BE 10 LBS MIN - 5 LBS READING AT THIS TIME, NEED CLARIFICATION FROM PLAN CHECK RE - THE USE OF 2 X 8 CEILING JOISTS INSTALLED AS OPPOSED TO 2 X 10 W/3/4 SHEATHING TO SUPPORT CEILING MOUNTED FURNACE AS SHOWN ON MECHANICAL PLAN DETAIL, BLOCK ALL REGISTER VENTS 3 WAYS MIN, TUB/SHOWERS NOT INSTALLED AT THIS TIME - NEED TO GROUT UNDER TUBS, GAS FLUE AT ATTIC MOUNTED FURNACE NOT COMPLETED AT THIS TIME, NAILL OFF SHEAR PANELS AT CORNERS & EVERY 25 ON EXTERIOR WALLS, REDHEAD SILL PLATES TO FLOOR AT ALL POSTS CARRYING ROOF LOAD, NEED HANGER AT REAR PORCH HIP RAFTER TO EXTERIOR WALL | |
12/14/1998 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000* |