Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/24/1998 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. GAS PRESSURE TEST WAS TO BE LEFT ON. 2. AT FINAL PUT SYSTEM UNDER PRESSURE WITH A GAUGE FOR PRESSURE TEST. 3. OLD BATHROOM NEEDS AN EXHAUST FAN WILL CHECK AT FINAL. |
| 08/14/1998 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. SEE UNIFORM PLUMBING CODE SECTION 1211.10. 2. USE RIGHT HAND / LEFT COUPLING ( LOUS PLUMBING) TO CONNECT NEW PIPE TO EXISTING LEAVE SHEET ROCK OPEN AN THAT CONNECTION TO VERIFY COUPLING. |
| 08/14/1998 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |
| 08/03/1998 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. USE RIGHT HAND/ LEFT COUPLING ( LOUS PLUMBING) TO CONNECT NEW PIPE TO EXISTING LEAVE SHEETROCK OPEN AN THAT CONNECTION TO VERIFY COUPLING. 2. BLOCK EACH SIDE OF VENT . 3. GROUNDING ELECTRIC RODE CONDUCTOR TO BE ONE PIECE OF WIRE OR CAP WELD . |
| 08/03/1998 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
PARTIAL APPROVAL |
| 07/20/1998 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. 3/4 METAL PIPE GAS OR H2O NOT ALLOWED UNDER SLAB. 2. PROTECT ALL PLUMBING FROM SHEET ROCK NAILS. |
| 07/20/1998 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |