Permit: T98CM01680

Parcel: 111071680

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
12/15/2000 PLUMBING - ABOVE CEILING Approved
03/04/2000 PLUMBING - ABOVE CEILING Correction Required ADDTL COMMS - 1. UNIT #2 WASTE AND VENT SYSTEM OK 2. UNIT #2 WATER DISTRIBUTION OK 3. UNIT #2 OK TO DRYWALL 4. UNIT #1&3 ROUGH PLDG AND INTERMEDIATE DENIED MUST HAVE 2 WASTE LINE FOR KIT SINK 5. NOTE: YOU CAN ONLY WET VENT 2 FIXTURE UNITS ON A VERTICAL WET VENT 6. EXSISTING WATER CLOSET MUST HAVE MIN 2 VTR
03/04/2000 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
02/09/2000 PLUMBING - ABOVE CEILING Correction Required ADDTL COMMS - 1. 1 1/2 DIRTY ARM FOR KITCHEN SINK EXCEEDS TOTAL DEVELOPED LINGTH MAX 42 2. DIRTY ARM HAS MORE THAN 135 DEGREE WILL REQUIRE C.O. 3. MIN. WASTE LINE FOR 2 FIXTURE UNITS IS 2 4. CAN NOT USE FERNCO COUPLINGS INSIDE OF STRUCTURE MUST USE SPECIALTY COUPLING 5. MUST TEST SYSTEM 42 HEAD
02/09/2000 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0000*