Inspection Status: Correction Required
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2000 |
PLUMBING - ROUGH, SOIL |
|
Correction Required |
ADDTL COMMS - 1. SOIL WATER TEST OK 2. OK TO BACKFILL AND CONCRETE 3. WILL REQUIRE REVISED AND APPROVED DRAWING FOR WASTE AND VENT SYSTEM BEFORE FINAL |
| 03/10/2000 |
PLUMBING - ROUGH, SOIL |
|
Correction Required |
ADDTL COMMS - 1. SOIL WATER TEST OK 2. FERNCO COUPLING @ P.O.C. FOR BLDG. DRAIN WILL BE ACCEPTED DUE TO EXSISTING BLDG DRAIN MATERIAL IS NO LONGER MADE AND THERE IS NO TRANSISTION COUPLING FOR THIS APPLICATION. 3. OK TO BACKFILL TRENCH 4. WILL REQUIRE REVISED AND APPROVED DRAWING FOR WASTE AND VENT SYSTEM BEFORE FINAL 5. OK TO FLAT VENT SYSTEM DUE TO ELEVATION OF EXSISTING BLDG. DRAIN 6. NOTE: THIS INSPECTION IS FOR UNIT #3 ONLY |
| 03/10/2000 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
PARTIAL APPROVAL |
| 03/04/2000 |
PLUMBING - ROUGH, SOIL |
|
Correction Required |
ADDTL COMMS - UNIT #2 WASTE AND VENT SYSTEM OK UNIT #2 WATER DISTRIBUTION OK UNIT #2 OK TO DRYWALL UNIT #1 AND 3 ROUGH PLDG AND INTERMEDIATE DENIED MUST HAVE 2 WASTE LINE FOR KIT SINK NOTE: YOU CAN ONLY WET VENT 2 FIXTURE UNITS ON A VERTICAL WET VENT 6. EXSISTING WATER CLOSET MUST HAVE MIN 2 VTR. |
| 03/04/2000 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000* |