Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T98CM01587
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2000 | ELECTRIC - FINAL | Partial Approval | COULD NOT LOCATE WA BOND | |
01/24/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. PERMANENTLY MARK SW BOARD 2. PNL B NEED 100A CB TO TRAN 3. T5 KVA TRANS TIE UFER TO NEUT 4. COMPLY NOTE #2 E-4 5. PERMANENTLY MARK 600P&1200 DISCS 6. NO WATER BOND | |
01/24/2000 | ELECTRIC - FINAL | Denied | DENIED | |
12/29/1999 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - FOR SERVICE ONLY APPROVED FOR TEMP POWER SUBJECT TO BOND | |
12/29/1999 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |