Permit: T98CM01568

Parcel: 12107043A


Addresses:

6031 E BELLEVUE ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/06/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/07/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/1. NEED GFC IN GARAGE. 2. BOND ALL METAL BOXES. 3. PROTECT ENDS OF CONDUIT FROM WIRE. 4. RUN CONDUIT INTO BOX FOR LIGHTS. 5. DRYER/RANGE 4 WIRES EACH HOME RUN. 6. THHN SINGLE STRAND NEEDS TO BE IN CONDUIT. 7. ALL J-BOX HAVE TO BE ACCESSIBLE 8. HOT NEUTRALS REVERSED. 9. ROMEX IN LAUNDRY TO BE PROTECTED.
02/05/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. NEED TO SEE BOTH ENDS OF YOUR CIRCUITS, ON ONE HOME 2. NEED ROMEX CONNECTORS AND BUSHINGS AT ALL METAL BOXES. 3. SUB-PANEL AND RANGE REQ. 4 WIRE CABLE, 2 HOT, NEUTRAL AND GROUND. 4. CAN'T RUN AWG SINGLE WIRE IF NOT IN CONDUIT. 5. ALL METAL BOXES NEED A BONDING JUMPER AND GREEN GROUND SCREW. 6. GARAGE OUTLETS TOO BE GFCI PROTECTED. 7. ALL WIRE TOO BE PROTECTED TO CEILING HT. 8. HOT AND NEUTRALS REVERSED IN GARAGE OUTLETS DON'T USE THEM.