Permit: T98CM01541

Parcel: 141203920

Inspection Status: Correction Required

Inspection History: FRAMING

Date Description Inspector Results Comments
05/27/1998 FRAMING Correction Required ADDTL COMMS - 1. SECOND FLOOR SHEAR WALLS DO NOT LAND ON FLOOR TRUSSES AND ARE NOT STRAPPED TO FLOOR TRUSSES PER PLAN. PROVIDE C.O.T AND ARCHITECT APPROVED REPAIR DOCUMENTS.
05/27/1998 FRAMING Partial Approval PARTIAL APPROVAL
05/26/1998 FRAMING Correction Required ADDTL COMMS - 1. CONDENSATE LINE TERMINATING TO LAUNDRY TRAP INADEQUATE (CANNOT DRAIN UPSTAIRS). 2. FURNACE FLUTE 2ND FLOOR MIN 1 FROM COMBUSTIBLES. 3. FURNACE FLUTE FROM 1ST FLOOR TERMINATING THROUGH ROOF MIN 1 FROM COMBUSTIBLES. 4. TRUSSES ABOVE KITCHEN AREA TOP CORD APROX 2 FROM LEDGER BOTTOM CORDS OVER NOTCHED AND SPLINTERED. 5. WATER LINES LEAKING IN KITCHEN AREA. 6. TRUSSES ABOVE LIVING ROOM TO LEDGER NEEDS TO BE COMPLETELY NAILED. 7. NO TRUSS DRAWINGS AVAIL. STOPPED INSPECTION.
05/26/1998 FRAMING Denied DENIED
05/26/1998 FRAMING Denied DENIED
05/21/1998 FRAMING Denied DENIED
05/18/1998 FRAMING Denied DENIED