Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/27/1998 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. SECOND FLOOR SHEAR WALLS DO NOT LAND ON FLOOR TRUSSES AND ARE NOT STRAPPED TO FLOOR TRUSSES PER PLAN. PROVIDE C.O.T AND ARCHITECT APPROVED REPAIR DOCUMENTS. |
| 05/27/1998 |
FRAMING |
|
Partial Approval |
PARTIAL APPROVAL |
| 05/26/1998 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. CONDENSATE LINE TERMINATING TO LAUNDRY TRAP INADEQUATE (CANNOT DRAIN UPSTAIRS). 2. FURNACE FLUTE 2ND FLOOR MIN 1 FROM COMBUSTIBLES. 3. FURNACE FLUTE FROM 1ST FLOOR TERMINATING THROUGH ROOF MIN 1 FROM COMBUSTIBLES. 4. TRUSSES ABOVE KITCHEN AREA TOP CORD APROX 2 FROM LEDGER BOTTOM CORDS OVER NOTCHED AND SPLINTERED. 5. WATER LINES LEAKING IN KITCHEN AREA. 6. TRUSSES ABOVE LIVING ROOM TO LEDGER NEEDS TO BE COMPLETELY NAILED. 7. NO TRUSS DRAWINGS AVAIL. STOPPED INSPECTION. |
| 05/26/1998 |
FRAMING |
|
Denied |
DENIED |
| 05/26/1998 |
FRAMING |
|
Denied |
DENIED |
| 05/21/1998 |
FRAMING |
|
Denied |
DENIED |
| 05/18/1998 |
FRAMING |
|
Denied |
DENIED |