Permit: T98CM01498

Parcel: 123150670


Addresses:

921 E LEE ST

Inspection Status: Correction Required

Inspection History: FRAMING

Date Description Inspector Results Comments
01/24/2000 FRAMING Correction Required ADDTL COMMS - 1. IMPROPER VENT CONNECTION FOR KITCHEN SINK. LAUNDRY 2ABS NOT ALLOWED TO SLIP OVER 1/2 GALVANIZED. 2. LAUNDRY TRAP ARM 2 EXCEEDS 60 INCHES TO VENT. 8 FOOT. 3. LAUNDRY BOX CANNOT BE GREATER THABN 36 TO TRAP. 4. P.E.X. CONNECTIONS IMPROPERLY MADE-MUST BE WITHIN OF STOP AND COLLAR MUST EXTEND TO END OF TUBING. 5. GALVANIZED PIPE CANNOT BE CONNECTED TO COPPER. USE BRASS OR PIELECTRIC UNION. 6. BLACK PIPE CANNOT BE IN POTABLE WATER SYSTEM. 7. BACK GROUT/SEAL FLOOR PENETRATIONS FOR TUB/SHOWER. 8. SHOWER DOES NOT HAVE TEMPORARY BALANCE VALVES. 9. BATH EXHAUSE DUCTS CANNOT BE PLASTIC. 10.P.E.X. CANNOT BE WITHIN 12 OF RECESSED LIGHTS. 11.W/C SHOWER VENT TS INSTALLED UPSIDEDOWN. 12.TUB AND SHOWER NOT IN PLACE. 13.TAPE NOT ALLOWED ON P.E.X. STOPPED INSPECTION.
01/24/2000 FRAMING Partial Approval IVRS - Inspection 0000*
11/22/1999 FRAMING Denied DENIED