Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2000 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. IMPROPER VENT CONNECTION FOR KITCHEN SINK. LAUNDRY 2ABS NOT ALLOWED TO SLIP OVER 1/2 GALVANIZED. 2. LAUNDRY TRAP ARM 2 EXCEEDS 60 INCHES TO VENT. 8 FOOT. 3. LAUNDRY BOX CANNOT BE GREATER THABN 36 TO TRAP. 4. P.E.X. CONNECTIONS IMPROPERLY MADE-MUST BE WITHIN OF STOP AND COLLAR MUST EXTEND TO END OF TUBING. 5. GALVANIZED PIPE CANNOT BE CONNECTED TO COPPER. USE BRASS OR PIELECTRIC UNION. 6. BLACK PIPE CANNOT BE IN POTABLE WATER SYSTEM. 7. BACK GROUT/SEAL FLOOR PENETRATIONS FOR TUB/SHOWER. 8. SHOWER DOES NOT HAVE TEMPORARY BALANCE VALVES. 9. BATH EXHAUSE DUCTS CANNOT BE PLASTIC. 10.P.E.X. CANNOT BE WITHIN 12 OF RECESSED LIGHTS. 11.W/C SHOWER VENT TS INSTALLED UPSIDEDOWN. 12.TUB AND SHOWER NOT IN PLACE. 13.TAPE NOT ALLOWED ON P.E.X. STOPPED INSPECTION. |
| 01/24/2000 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 11/22/1999 |
FRAMING |
|
Denied |
DENIED |