Permit: T98CM01324

Parcel: 127010290

Inspection Status: Correction Required

Inspection History: ROOF NAILING

Permit Number - T98CM01324

Inspection Description - ROOF NAILING

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/28/1998 ROOF NAILING Correction Required ADDTL COMMS - 1. VERIFY THAT H2O LINES ARE NOT OVER LOADING SYSTEM AFTER COMING OFF A 3/4 H2O LINE YOU CAN HAVE 3 FIXTURES ON THAT 1/2 LINE NO MORE. 2. USE COPPER OR BRASS PLUG AT SHOWER NO THREADED JOINTS TO BE CONCELED. 3. MAKE UP ALL ELECT BOXES, GRDS, NEUTRALS. 4. PER PLAN YOU NEED A BATHROOM EXHAUST FAN. 5. YOU NEED 2 METAL AT PLATE LINE SEE YOU STUCCO INSTALLATION SHEET FOR DETAILS. 6. ADD BLOCKS AT EXISTING WALL AND SECURE NEW WALL. 7. CIRCUIT FOR BATHROOM OUTLET TO BE BY ITSELF NO OTHER OUTLETS ALLOWED. 8. 14 GAUGE WIRE OLD SPRINKLER CIRCUIT TO BE REMOVED.