Inspection History Details
Inspection Status: Correction Required
Inspection History: ROOF NAILING
Permit Number - T98CM01324
Inspection Description - ROOF NAILING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/28/1998 | ROOF NAILING | Correction Required | ADDTL COMMS - 1. VERIFY THAT H2O LINES ARE NOT OVER LOADING SYSTEM AFTER COMING OFF A 3/4 H2O LINE YOU CAN HAVE 3 FIXTURES ON THAT 1/2 LINE NO MORE. 2. USE COPPER OR BRASS PLUG AT SHOWER NO THREADED JOINTS TO BE CONCELED. 3. MAKE UP ALL ELECT BOXES, GRDS, NEUTRALS. 4. PER PLAN YOU NEED A BATHROOM EXHAUST FAN. 5. YOU NEED 2 METAL AT PLATE LINE SEE YOU STUCCO INSTALLATION SHEET FOR DETAILS. 6. ADD BLOCKS AT EXISTING WALL AND SECURE NEW WALL. 7. CIRCUIT FOR BATHROOM OUTLET TO BE BY ITSELF NO OTHER OUTLETS ALLOWED. 8. 14 GAUGE WIRE OLD SPRINKLER CIRCUIT TO BE REMOVED. |