Permit: T98CM00715

Parcel: 126210180

Inspection Status: Correction Required

Inspection History: FRAMING

Permit Number - T98CM00715

Inspection Description - FRAMING

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/11/1998 FRAMING Correction Required ADDTL COMMS - APPROVED SUBJECT TO THE APPROVAL OF TJI AND ENGINEERS LETTER REGARDING NEW & AS BUILT SYSTEM FOR CEILING AND ROOF CHANGES
07/23/1998 FRAMING Correction Required ADDTL COMMS - CEILING 1/4X20 EYE LAG SCREWS HAVE BEEN SCREWED INTO BOTTOM CORD OF TJI TRUSSES. THIS PROHIBITED AS DAMAGE TO BOTTOM CORD HAS OCCURRED. PROVIDE TJI INFO ON PROPER WAY TO HANG PIPES, CEILING RAILS,ETC FROM TJI TRUSSES ( IF AVAILABLE). INCLUDE INTERMEDIATE PLUMBING, ELECTRIC, AND MECH IN NEXT INSPECTION REQUEST. DO NOT COVER OR PLASTER PORCH CEILING WITHOUT PROOF REQUEST REGARDING TJI TRUSSES.
07/23/1998 FRAMING Denied DENIED
05/08/1998 FRAMING Denied DENIED