Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/19/2000 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. FURNACE GAS CONNECTOR CANNOT EXCEED 36" IN LENGTH. 2. UNDERSIZE FURNACE PLAN REQUIRES 125000 BTU BUT ONLY 100,000 INSTALLED. 3.. BATH EXHAUST FANS DO NOT OPERATE. NOTE: THE FOLLOWING ITEMS ALSO EXIST BEFORE THE HOUSE WILL BE COMPLETE. KITCHEN COUNTERS MUST HAVE GFCI OUTLETS WITHIN 24" OF RANGE AND EVERY 48" ALONG WALL THEREAFTER, BATHROOM UPSTAIRS JACCUZI TUB CANNOT HAVE LIGHT SWITCHES WITHIN 60" OF TUB, JACCUZI TUB MUST BE ON A DEDICATED GFCI CIRCUIT, ALL STAIR RISERS MUST BE WITHIN 3/8" TOTAL DIFFERENCE IN HEIGHT, HALL BATH CEILING MUST BE 7 FT IN HEIGHT. PRESENTLY 6' 5" COMPLETE ALL ELECTRIC SWITCHES AND OUTLETS, WINDOWS SIZES AND SILL HEIGHTS ARE NOT PER PLAN, NEED ADDRESS ON HOUSE MINIMUM 3" HIGH NUMBERS, PAINT ABS PLASTIC VENTS ON ROOF, ADD SKYLIGHT IN KITCHEN TO PLAN. FINISH ALL BATHROOMS, PLAN CALLS FOR REMOVAL OF LIVING ROOM SOFFET. PLEASE BUILD TO PLAN OR REVISE PLAN TO AS BUILT AND HAVE APPROVED BY CITY OF TUCSON. |
| 10/16/2000 |
MECHANICAL - FINAL |
|
Cancelled |
IVRS - Ri canceled |