Date Description Inspector Results Comments
11/03/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MULTI POLE LUG TERMINATIONS
2. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING
3. NO MORE THAN 360 DEG. IN A CONDUIT RUN
4. BOX HAS DETACHED FROM WALL AND CONDUIT HAS DETERIORATED AWAY.
5. VERIFY IF THIS IS A HAZARDOUS LOCATION
6. VERIFY AUDIO/VISUAL ALARMS.