Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MULTI POLE LUG TERMINATIONS 2. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 3. NO MORE THAN 360 DEG. IN A CONDUIT RUN 4. BOX HAS DETACHED FROM WALL AND CONDUIT HAS DETERIORATED AWAY. 5. VERIFY IF THIS IS A HAZARDOUS LOCATION 6. VERIFY AUDIO/VISUAL ALARMS. |