Inspection History Details
Inspection Status: Correction Required
Inspection History: BUILDING - FINAL
Permit Number - T98CM00174
Inspection Description - BUILDING - FINAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/1999 | BUILDING - FINAL | Correction Required | ADDTL COMMS - 1. PANEL NOT GROUNDED. 2. BAD GFCI BREAKER IN GARAGE. 3. VACUUM BREAKER NEEDED ON FRONT HOSE BIB. | |
01/28/1999 | BUILDING - FINAL | Denied | IVRS - Inspection 0999* | |
11/12/1998 | BUILDING - FINAL | Denied | IVRS - Inspection 0999* | |
11/10/1998 | BUILDING - FINAL | Correction Required | ADDTL COMMS - ADJUST SELF CLOSER AT GARAGE/ HOUSE DOOR. 1. INSTALL 90 DEGREE FITTING AT EXTERIOR PTR OUTSIDE OF GARAGE. 2. 1 GOUND WIRE PER LUG IN MAIN PANEL. 3. GAS FLUE INCOMPLETE FOR WATER HEATER. 4. LABEL ALL CIRCUITS IN MAIN PANEL AND IF PLUMBED IN PLASTIC PIPE MAKE NOTE IN PANEL. IF COPPER PLUMBING NEED WATER BOND. 5. NEED TO INSTALL BOND WIRE BETWEEN DUCTS ABOVE FURNACE. 6. PLASTIC LAUNDRY BOX NOT ALLOWED IN FIRE WALL BETWEEN GARAGE AND HOUSE ON GARAGE SIDE. NEED METAL FIRE RATED BOX. | |
11/10/1998 | BUILDING - FINAL | Denied | DENIED | |
11/03/1998 | BUILDING - FINAL | Correction Required | ADDTL COMMS - BUILDING LOCKED, NO ONE ANSWERS DOOR | |
11/03/1998 | BUILDING - FINAL | Denied | DENIED |