Permit: T98CM00109

Parcel: 118072600

Inspection Status: Correction Required

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/29/1998 BUILDING - FINAL Correction Required ADDTL COMMS - 1. PTR AT WATER HEATER NEEDS TO GO TO DAYLIGHT AND NOT BE CONNECTED TO WASTE LINE. 2. NEED TO HAVE GAS COCK FLEX HOSE ON AND CAPPED AT DRYER. 3. FUSED OUTLET REQUIRED AT FURNACE (SRU). 4. WATER BOND REQUIRED FROM COLD WATER PIPING TO MAIN ELECT PANEL. IF WATER PIPING IS ALL COPPER. IF PLUMBED IN PLASTIC WATER PIPING. WRITE INSIDE MAIN ELECT PANEL PLUMBED IN PLASTIC PIPE.
12/29/1998 BUILDING - FINAL Denied DENIED
12/16/1998 BUILDING - FINAL Correction Required ADDTL COMMS - INSTALL W/P RECEPTACLE COVER ON PLUG AT SOUTH SIDE AND ADD AN SNTI SIPHON ADAPRTO TO HOSE BIBB ON NORHT SIDE
12/16/1998 BUILDING - FINAL Denied IVRS - Inspection 0999*