Inspection History Details
Inspection Status: Correction Required
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T98BU02475
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/1999 | POOL/SPA FINAL/BARRIER | Correction Required | ADDTL COMMS - CONTRACTOR CAN PLASTOR | |
02/23/1999 | POOL/SPA FINAL/BARRIER | Correction Required | ADDTL COMMS - 1. MIN 48 FROM POOL WATER EDGE TO GROUND. 2. NO BOND TO BARRIER FROM POOL. NOTE: BOND HAS TO ALSO CONNECT THROUGH GATE. 3. POOL/MASONRY/WROUGHT IRON AREA MIN 48 RADIUS AT THIS AREA. | |
02/23/1999 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection 0999* |