Permit: T98BU00637

Parcel: 141133300

Inspection Status: Correction Required

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
06/19/1998 POOL/SPA FINAL/BARRIER Correction Required ADDTL COMMS - 1. POOL GATE MUST BE SELF CLOSING AND LATCHING PRESENTLY GATE BINDS ON STRIKER POST. 2. METAL FENCING WITHIN 5 FEET OF POOL MUST BE ELECTRICALLY BONDED TO POOL EQUIPMENT WITH PROPER BONDING CONNECTORS AND MACHINE SCREWS WITH NUTS. DO NOT USE SELF TAPING SCREWS. 3. AN EXCESS OF 4 INCH OPENING EXISTS BETWEEN BOTTOM OF FENCE AND NATURAL GRADE.
06/19/1998 POOL/SPA FINAL/BARRIER Denied DENIED