Permit: T97OT00202


Addresses:

1902 W PRICE ST

Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/07/1997 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1:REINSTALL ALL FIXTURES.2:REPLACE ALL BROKEN RECPTACLES.3:SEAL OPEN HOLE AT DISCONNECT SW SO-WEST REPAIR AREA.4:REPAIR ALL FIXTURES IN AUTO REPAIR AREA.5:OBTAIN AN L-11 LICENSED CONTRACTOR TO REPAIR AND RETERMINATE WIRING AT ALL THREE PANELS AT NORTH EAST AREA OF AUTO RERAIR AREA,CLEAN ALL PANEL TERMINATIONS,INSTALL COVERS.6:REPLACE BURNT WIRING AT GUTTER ON SOUTH WALL AUTO REPAIR AREA,REPLACE BROKEN RECEPTS THIS AREA ALSO.7:SPRAY BOOTH OK BUT AREA WHERE PAINT MIXED IS CONSIDERED A CLASSIFIED AREA,WHER YOU ARE REQUIRED TO USE SPECIAL WIRING METHODS,SPEAK TO RANDY SCHULER DSC CITY OF TUCSON ELECTRICAL PLANS EXAMINER,791-5550.8:HAVE AN ELECTRICAL CONTRACTOR OBTAIN A 2-HOUR GENERAL PERMIT AND DO WORK.CALL FOR A FINAL WHEN WORK COMPLETED.RAY MAJUTA E-21 DSC
10/07/1997 ELECTRIC - FINAL Denied