Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/07/1997 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1:REINSTALL ALL FIXTURES.2:REPLACE ALL BROKEN RECPTACLES.3:SEAL OPEN HOLE AT DISCONNECT SW SO-WEST REPAIR AREA.4:REPAIR ALL FIXTURES IN AUTO REPAIR AREA.5:OBTAIN AN L-11 LICENSED CONTRACTOR TO REPAIR AND RETERMINATE WIRING AT ALL THREE PANELS AT NORTH EAST AREA OF AUTO RERAIR AREA,CLEAN ALL PANEL TERMINATIONS,INSTALL COVERS.6:REPLACE BURNT WIRING AT GUTTER ON SOUTH WALL AUTO REPAIR AREA,REPLACE BROKEN RECEPTS THIS AREA ALSO.7:SPRAY BOOTH OK BUT AREA WHERE PAINT MIXED IS CONSIDERED A CLASSIFIED AREA,WHER YOU ARE REQUIRED TO USE SPECIAL WIRING METHODS,SPEAK TO RANDY SCHULER DSC CITY OF TUCSON ELECTRICAL PLANS EXAMINER,791-5550.8:HAVE AN ELECTRICAL CONTRACTOR OBTAIN A 2-HOUR GENERAL PERMIT AND DO WORK.CALL FOR A FINAL WHEN WORK COMPLETED.RAY MAJUTA E-21 DSC |
| 10/07/1997 |
ELECTRIC - FINAL |
|
Denied |
|