Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | ELECTRIC - FINAL | Partial Approval | ALL ITEMS EXCEPT #2 COMPLETE, OWNER TO VERIFY COMPLIANCE W/NEC 2002, #110-3 LISTING OF PAY STATION PER OSHA APPROVED TESTING FACILITY. |
|
| 07/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 8:30-9:00 AM DANNY CARIZOZA - SERVICE TECHNICIAN FROM COCHISE PETROLEUM (602) 721-2529 CALLED, HE IS ON SITE JUST STARTING TO ATTEMPT TO MAKE CORRECTIONS, CANNOT FIND APPROVED LISTING ON PAY STATION, STARTING TO MAKE ONE LINE DIAGRAM, DISCUSSED ALL ITEMS LISTED ABOVE WILL CORRECT & RECALL. |
|
| 07/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A ONE LINE DIAGRAM OF CIRCUITS TO STATIONS. 2. VERIFY APPROVED LISTING OF PAYSTATION AT ISLANDS, UL, ETC CSA OTHER 3. GROUND ALL J-BOXES AT ISLANDS 4. SEAL ALL EYS FITTING AT ISLANDS & MAIN PNL INSIDE 5. INSTALL COMMUNICATIONS WIRING IN FLEX AT STATIONS VERIFY COMMUNICATION WIRING 120V CIRCUITS OK TO OCCUPY SAME J-BOX. 6. WHEN REINSPECTION IS CALLED FOR HAVE CONTRACTOR MEET INSPECTOR ON SITE TO OPEN EQUIPMENT. |