Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/09/1999 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/08/1998 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - GROUND ALL METAL ELEC BOXES, ELEC OUTLETS TO BE MAX 12 APART, CANNOT LOCATE BASEBOARD HEATER UNDER ELEC OUTLETS, ALL JUNCTION BOXES TO BE ACCESSIBLE, ELEC OUTLETS & SWITCHES NOT PER PLAN, REMOVE ALL UNUSED ELEC WIRES, SUBPANEL TO HAVE 15 CLEAR WORKING SPACE BOTH SIDES CENTER OF SUBPANEL BOX. |
| 12/08/1998 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |