Permit: T97CM03503

Parcel: 136383240


Addresses:

7217 E MARIGOLD CI

Inspection Status: Correction Required

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/16/1998 BUILDING - FINAL Correction Required ADDTL COMMS - WALL ONLY COMPLETE - REAR PATIO APPROVED. (2) 2 POLE 40 AMP BREAKERS PROTECTING (2) #10 CO WIRE CIRCUITS, SUBPANEL REQUIRES A SEPARATE GROUND BUSS ISOLATE NEUTRALS FROM GROUNDS, TWO BASEBOARD HEATERS RATED AT 7.2 AMPS WHEN WIRED AT 220 VOLTS, TAKE 30 2 POLE IN SUBPANEL CHANGE TO TWO POLE 20 AMPS, RUN WIRE FROM WALL IN BACK OF HEATER - SEE DRAWING
10/16/1998 BUILDING - FINAL Partial Approval PARTIAL APPROVAL
09/28/1998 BUILDING - FINAL Correction Required ADDTL COMMS - 1. NO ONE HOME. 2. WHAT PART OF THIS PERMIT DO YOU WANT INSPECTED. 3. IF ITS JUST FOR THE ROOM LET ME KNOW I WILL NEED ACCESS. 4. IF ITS FOR THE WALL I NEED TO KNOW THAT ALSO. 5. LEAVE INSPECTION REPORT FOR FOOTING.
09/28/1998 BUILDING - FINAL Not ready for Inspection NOT READY FOR INSPECTION
02/02/1998 BUILDING - FINAL Correction Required ADDTL COMMS - 1. BASEBOARD HEATERS FED OFF 60 AMP SUB- MAIN DBL. 2. YOU HAVE WALL INSTALLED THAT NOT ON YOUR FLOOR PLAN. THIS ROM THAT EXISTS INTO ANOTHER ROOM NEEDS TO BE ON FLOOR PLAN. 3. WIRING AT EXT NEED TO BE PROTECTED FROM THE SUN LIGHT AND PHYSICAL DAMAGE.
02/02/1998 BUILDING - FINAL Not ready for Inspection NOT READY FOR INSPECTION
12/30/1997 BUILDING - FINAL Not ready for Inspection NOT READY FOR INSPECTION