Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/10/2000 |
FRAMING |
|
Cancelled |
IVRS - Ri canceled |
| 10/20/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF STUD SURFACE. 2. FIRE BLOCK FURRED OUT WALLS AT TOP PLATE AND EAST AND WEST WALLS. 3. BACK GROUT FLOOR PENETRATION FOR TUB. 4. TUB HAS COMPRESSION CONNECTION DRAIN KIT. EITHER PROVIDE AN ACCESS PANEL OR CHANGE DRAIN KIT TO A GLUED FITTING UNIT. 5. BATHROOM GFCI OUTLET MUST BE ON A DEDICATED 20 AMP CIRCUIT WITH 12 GAUGE WIRES. 6. SHOWER REQUIRES A PRESSURE/TEMPERATURE BALANCE VALVE OR APPROVED ANTI SCALD DEVICE. 7. FURNACE "B" VENT REQUIRES 1" TO COMBUSTABLES ON TAPE DOUBLE VENT. 8. WATER HEATER T AND P LINE MUST EXHAUST OUTSIDE. 9. W/H GAS VLAVE MUST BE ACCESABLE INSTALL LISTED VALVE. 10. VENT LAUNDRY. |
| 05/09/2000 |
FRAMING |
|
Correction Required |
ADDTL COMMS - NOT READY |
| 05/09/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |