Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/12/1999 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. TRUSS REPAIR-NOT NAILED TO PLAN |
| 01/12/1999 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 11/27/1998 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/30/1998 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. NEED TRUSS REPAIR DRAWING FOR TRUSSES THAT HAVE BEEN CUT AT TOP CORDS FROM TRUSS MANUFACTURE AND HAVE CITY APPROVE REPAIR DRAWINGS. 2. INSTALL X BRACING IN TRUSSES AT BOTH ENDS AND MIDDLE. 3. INSTALL LATERAL BRACING ON TRUSS WEBBS PER TRUSS DRAWINGS. 4. BLOCK RIDGE LINE PER PLANS AND INSTALL LATERAL BRACING AT ENDS. 5. TRUSS I.D #4 IS NON STRUCTURAL AND NEEDS CONTINIOUS SUPPORT AT BOTTOM CORD. TRUSS I.D. #1 NEEDS TO HAVE BEARING UNDER STUBBED END. BOTH TRUSSES AT FRONT ENTRY. HAVE TRUSS ENGINEER DESIGN FIX IN THIS AREA. 6. TRUSSES OVER ENTRY DONT HAVE BEARING WALL, NO FOOTINGS AT ENTRY AREA NEED TO REDESIGN. |
| 10/30/1998 |
FRAMING |
|
Denied |
DENIED |