Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/1998 |
ELECTRIC - FINAL |
|
Denied |
CORRECTIONS REQ SEE LIST |
| 11/24/1997 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - OK TEMP C OF O PER R MAJUTA,STILL NEED 200 A CLASS R FUSING FOR PANELS ALSO REJECT CLIPS INSTALL INSULATING MATERIAL PERMANENTLY BETWEEN ALL FUSES IN SWITCH GEAR AND OUTSIDE FUSES ID ALL PANELS AND INSTALL SCHEDULES ID ALL SWITCHES CONTINUE TO ISOLATE NEUTRALS AND EQMT GRDS IN NEW PNLS,BEING DONE AS I INSPECT REMOVE GREEN GRDING SCREW ON INSIDE PANELS BOND GRD TERMINAL TO CAN IN PANELS GET APPROVED REVISIONS THUR ENG |
| 11/24/1997 |
ELECTRIC - FINAL |
|
Partial Approval |
OK TEMP C OF O ONLY |