Permit: T97CM03340

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/02/1998 ELECTRIC - FINAL Denied CORRECTIONS REQ SEE LIST
11/24/1997 ELECTRIC - FINAL Correction Required ADDTL COMMS - OK TEMP C OF O PER R MAJUTA,STILL NEED 200 A CLASS R FUSING FOR PANELS ALSO REJECT CLIPS INSTALL INSULATING MATERIAL PERMANENTLY BETWEEN ALL FUSES IN SWITCH GEAR AND OUTSIDE FUSES ID ALL PANELS AND INSTALL SCHEDULES ID ALL SWITCHES CONTINUE TO ISOLATE NEUTRALS AND EQMT GRDS IN NEW PNLS,BEING DONE AS I INSPECT REMOVE GREEN GRDING SCREW ON INSIDE PANELS BOND GRD TERMINAL TO CAN IN PANELS GET APPROVED REVISIONS THUR ENG
11/24/1997 ELECTRIC - FINAL Partial Approval OK TEMP C OF O ONLY