Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/23/1997 |
FRAMING |
|
Correction Required |
ADDTL COMMS - 1. CONNECTION OF SHEAR TRANSFER BLKS NOT PER PLAN. PLAN CALLS FOR BLOCKS NAILED + STC CLIP ON 2 SIDES @ SHEAR WALL #8 BETWEEN HOUSE AND GARAGE (BOTH WALLS). 2. SHEAR PANEL @ DOOR BTWN HOUSE AND GARAGE RIGHT SIDE IS DAMAGED AT TOP. REPLACE PANEL HAVE ELECTRICIAN DRILL 3/4 MAX HOLES FOR WIRE PENETRATIONS. 3. PATCH LATH, FOAM AND PAPER AT REAR BATH TUB. CAULK ALL PENETRATION THRU LATH AND FOAM ON LAST WALL. |
| 12/23/1997 |
FRAMING |
|
Denied |
DENIED |
| 12/22/1997 |
FRAMING |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |
| 12/16/1997 |
FRAMING |
|
Correction Required |
ADDTL COMMS - SHEAR TRANSFER @ #8 SHEAR WALL MISSING. CK PLATE BOLTS 24 OC MAX. #8 SHEAR WALL @ GARAGE/KITCHEN DOOR MISSING. FLEX NOT CONNECTED TO DISTRIBUTION BOX @ KIT/BEDRM. |
| 12/16/1997 |
FRAMING |
|
Denied |
DENIED |