Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/14/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999$/ 1) BAR WIRES AND NO LIGHT FIXTURES ON EXTERIOR OF GARAGE 2) ALL GARAGE ELECTRIC OUTLETS MUST BE GFCI PROTECTED 3) SHOP AND STORE-ROOM NOT COMPLETE 4) SEPARATE BUILDING WITH MORE THAN 1 ELECTRIC CIRCUIT REQUIRES A SEPARATE GROUNDING SYSTEM. INSTALL 2 EACH 8' GROUND RODS 6' OR MORE APART CONNECTED TO ELECTRIC SUB PANEL WITH A CONTINOUS #4 CONDUCTOR 5) ALL ELECTRIC OUTLETS MUST BE 18" OR HIGHER ABOVE FLOOR |