Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T97CM03083
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/14/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999$/ 1) BAR WIRES AND NO LIGHT FIXTURES ON EXTERIOR OF GARAGE 2) ALL GARAGE ELECTRIC OUTLETS MUST BE GFCI PROTECTED 3) SHOP AND STORE-ROOM NOT COMPLETE 4) SEPARATE BUILDING WITH MORE THAN 1 ELECTRIC CIRCUIT REQUIRES A SEPARATE GROUNDING SYSTEM. INSTALL 2 EACH 8' GROUND RODS 6' OR MORE APART CONNECTED TO ELECTRIC SUB PANEL WITH A CONTINOUS #4 CONDUCTOR 5) ALL ELECTRIC OUTLETS MUST BE 18" OR HIGHER ABOVE FLOOR |