Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T97CM03083

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
03/14/2002 BUILDING - FINAL Denied IVRS - Inspection 0999$/ 1) BAR WIRES AND NO LIGHT FIXTURES ON EXTERIOR OF GARAGE 2) ALL GARAGE ELECTRIC OUTLETS MUST BE GFCI PROTECTED 3) SHOP AND STORE-ROOM NOT COMPLETE 4) SEPARATE BUILDING WITH MORE THAN 1 ELECTRIC CIRCUIT REQUIRES A SEPARATE GROUNDING SYSTEM. INSTALL 2 EACH 8' GROUND RODS 6' OR MORE APART CONNECTED TO ELECTRIC SUB PANEL WITH A CONTINOUS #4 CONDUCTOR 5) ALL ELECTRIC OUTLETS MUST BE 18" OR HIGHER ABOVE FLOOR