Inspection Status: Denied
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/1997 |
PLUMBING - ROUGH, SOIL |
|
Denied |
DENIED A.M. INSPECTION |
| 09/04/1997 |
PLUMBING - ROUGH, SOIL |
|
Correction Required |
ADDTL COMMS - A. LOCATE EXISTING SEWER LINE, UNCOVER TO VERIFY DEPTH. B. DONT FLAT VENT FIXTURES NO NEED TO VENT JUST LIKE YOUR PLAN SHOWS, FROM VERTICAL VENT. C. LOWER SOIL LINES, ABS TO BE 12 BELOW GRADE MIN. THAT WILL ALLOW YOU TO VENT PROPERLY. D. GAS & WATER LINES TO BE RELOCATED-NOT UNDER SLAB. |
| 09/04/1997 |
PLUMBING - ROUGH, SOIL |
|
Denied |
DENIED |