Permit: T97CM02178

Parcel: 132164150


Addresses:

1750 E MISSOURI ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T97CM02178

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/11/2008 PLUMBING - INTERMEDIATE Approved REFERENCE PRE SLAB APPROVAL BY HENRY DURAZO 11/13/98
10/15/1998 PLUMBING - INTERMEDIATE Correction Required ADDTL COMMS - 1. COUPLINGS IN COPPER PIPING UNDER CONCRETE SLABS MUST BE SILVER SOLDERED. YOU MAY USE SOFT COPPER PIPING (IN ROLLS) WITHOUT COUPLINGS.
10/15/1998 PLUMBING - INTERMEDIATE Denied DENIED