Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T97CM02178
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2008 | PLUMBING - INTERMEDIATE | Approved | REFERENCE PRE SLAB APPROVAL BY HENRY DURAZO 11/13/98 | |
10/15/1998 | PLUMBING - INTERMEDIATE | Correction Required | ADDTL COMMS - 1. COUPLINGS IN COPPER PIPING UNDER CONCRETE SLABS MUST BE SILVER SOLDERED. YOU MAY USE SOFT COPPER PIPING (IN ROLLS) WITHOUT COUPLINGS. | |
10/15/1998 | PLUMBING - INTERMEDIATE | Denied | DENIED |