Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T97CM02023

Parcel: 130022130


Addresses:

1805 S 30TH PL


Inspection Status: Correction Required

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T97CM02023

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/09/1998 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - BUILDER WAS NOTIFIED ON PREVIOUS INSPECTION OF MISSING SUPPLY AIR REGISTER IN DINING AREA. IT IS ASSUMED THAT BUILDER WISHES TO PROCEED WITHOUT SAID VENT.
03/05/1998 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - 1. THE USER OF FLATTEND A2.5 STRAPS TO STRAP THE HEADERS TO THE TRIMMER AND KING STUD IS IMPROPRE. USE 2 NAIL LINE CS OR CST STRAPS ( MAY BE APPLIED TO INSIDE EA. SIDE). A 2.5 STRAPS ONCE FLATTENED HAVE NO LISTED UPLIFT VALUE AND ARE NOT A LISTED PRODUCT. 2. THE A35 STRAPS REQUIRE 12 8D NAILS ALL ARE UNDER NAILED. 3. THE A2.5 STRAPS ARE UNDER NAILED- SEE MFGRRS INSTRUCTIONS. 4. THE A 2.5 STRAPS NAILED FROM CENTER WALL TOP PLATES TO TJI TRUSSES REQUIRE THE USE OF WEB STIFFNERS- CORRECT ALL. 5. THE SUPPLY AOR REGISTERS TO DINING ROOM IS MISSING. 6. THE SUPPLY AIR REGISTERS REQUIRE 3 SIDES BLOCKED. CORRECT AND RECALL
03/05/1998 EXT METAL CLIPS/EXT SHEATHING Denied DENIED