Permit: T97CM01870

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/21/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000* OK FOR C OF O
02/08/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
MISSING TRIM AT WASHER BOX #1 AND 2 PVC NOT ALLOWED IN EXPOSED EXTERIOR LOCATIONS FOR HOSE BIBBS
GAS PRESSURE TEST OK #1&2
NO 90 DEGREE TURN DOWN ON T&P REFIEF DRAIN #1 &2
SQUARE HEAD CLEAN OUT PLUG IN SIDEWALK A TRIPPING HAZARD #1 AND 2 BREAK
VENTS WITHIN 10' OF AIR INTAKE ON ROOF TO BE RAISED #1 AND 2
#2 CLEAN OUT COVER NEEDED UNDER K.S. MAXIMUM 12" FLEX ON T&P DRAIN
11/30/1998 PLUMBING - FINAL Denied DENIED