Inspection History Details
Permit: T97CM01870
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* OK FOR C OF O | |
| 02/08/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* MISSING TRIM AT WASHER BOX #1 AND 2 PVC NOT ALLOWED IN EXPOSED EXTERIOR LOCATIONS FOR HOSE BIBBS GAS PRESSURE TEST OK #1&2 NO 90 DEGREE TURN DOWN ON T&P REFIEF DRAIN #1 &2 SQUARE HEAD CLEAN OUT PLUG IN SIDEWALK A TRIPPING HAZARD #1 AND 2 BREAK VENTS WITHIN 10' OF AIR INTAKE ON ROOF TO BE RAISED #1 AND 2 #2 CLEAN OUT COVER NEEDED UNDER K.S. MAXIMUM 12" FLEX ON T&P DRAIN |
|
| 11/30/1998 | PLUMBING - FINAL | Denied | DENIED |