Inspection History Details
Inspection Status: Closed
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2008 | BUILDING - FINAL | Closed | OK AS OFFICES. | |
| 01/10/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BEDROOM ON EAST SIDE IS OK FOR MINIMUM REQUIREMENTS 2) BEDROOM ON WEST SIDE EMERGENCY EGRESS WINDOW MUST HAVE MINIMUM AREA, PLUS 20" WIDE X 24" HT YOUR WINDOW IS 21" X 36" = APPOX 4.5 SQ FT YOU NEED 5.7 3) CANNOT LOCATE CIRCUIT BREAKER FOR POWER SOURCE FOR NEW ROOMS, RECEPTS TEST OUT OK PERMIT TAKEN OUT 6/28/97 ARC FAULT REQ. NOT IN ELECTRIC 4) PLEASE HAVE A SERVICE LOAD CALCULATED, A/C ADDED, PLUS H20 HTR CONVERTED FROM GAS 125 AMP SERV. MAX 5) YOU CAN HAVE BEDROOMS REMOVED FROM PERMIT AND CHANGED TO OFFICES 6) FOR FINAL ONLY/BUILT WITHOUT PERMITS OR INSPECTIONS |
|
| 10/17/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE NOTES FROM 1997 2. PROVIDE ACCESS 3. PROVIDE CORRECT CONTACT INFORMATION 1154 AM |
|
| 07/31/1997 | BUILDING - FINAL | Correction Required | ADDTL COMMS - WATER HEATER LOCATED IN BEDROOM. PLMBG. CODE SEC. 802 PROHIBITS GAS WTR. HEATER IN SLEEPING ROOMS. | |
| 07/31/1997 | BUILDING - FINAL | Denied |