Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/02/1997 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - OK TO INSULATE & SHEETROCK. YOU NEED A GRND WIRE INSIDE CONDUIT, FLEX CONDUIT NOT APPR AS A BOND, ONLY RIGID. |
| 12/02/1997 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
PARTIAL APPROVAL |
| 10/28/1997 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. 2 20AMP COUNTER TOP CIRCUITS REQD. 2. 1 20AMP CIRCUIT FOR DISPOSAL. 3. REFRIGERATOR, KIT LIGHT, 110 OUTLET FOR STOVE (GAS) CAN GO ON GENERAL LIGHTING CIRCUIT. 4. #4 COPPER 4WIRE FEEDER FOR 100AMP SUB PANEL. 5.BOND ALL METAL BOXES WITH A JUMPER TO GRD. |
| 10/28/1997 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |