Permit: T97CM01546

Parcel: 121071030


Addresses:

1631 N SONOITA AV

Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/02/1997 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - OK TO INSULATE & SHEETROCK. YOU NEED A GRND WIRE INSIDE CONDUIT, FLEX CONDUIT NOT APPR AS A BOND, ONLY RIGID.
12/02/1997 ELECTRIC - INTERMEDIATE Partial Approval PARTIAL APPROVAL
10/28/1997 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. 2 20AMP COUNTER TOP CIRCUITS REQD. 2. 1 20AMP CIRCUIT FOR DISPOSAL. 3. REFRIGERATOR, KIT LIGHT, 110 OUTLET FOR STOVE (GAS) CAN GO ON GENERAL LIGHTING CIRCUIT. 4. #4 COPPER 4WIRE FEEDER FOR 100AMP SUB PANEL. 5.BOND ALL METAL BOXES WITH A JUMPER TO GRD.
10/28/1997 ELECTRIC - INTERMEDIATE Not ready for Inspection NOT READY FOR INSPECTION