Inspection History Details
Inspection Status: Correction Required
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T97CM01078
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/1997 | EXT METAL CLIPS/EXT SHEATHING | Correction Required | ADDTL COMMS - 1. PLYWOOD ON EXT. TO BE GLUED & SCREWED TO STUDS, SEE 3/A2.1. 2. PLYWOOD NOT ATTACHED TO TOP PLATE. 3. BUTT JOINTS @ PLYWOOD NOT NAILED IN AREAS, NEED BLOCKING. CHECK ALL. 4. S.WEST CORNER OF BUILDING-PLYWOOD NOT NAILED. 5. CONSULT ARCH. 0OF RECORD REGARDING THE MANNER IN WHICH PLYWOOD HAS BEEN FASTENED TO STUDS. GET WRITTEN, STAMPED APPROVAL IF ACCEPTABLE. 6. HAVE ON SITE AT NEXT INSPECTION.7. ANY MASONRY OR CONCRETE FOOTINGS NEED INSPECTION. | |
08/08/1997 | EXT METAL CLIPS/EXT SHEATHING | Denied | DENIED |