Permit: T97CM00977

Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/25/1997 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - OK TO COVER UNDERGROUND - YOU MUST INSTALL 2 EACH GROUND RODS 8 FEET LONG INSTALLED 6 FEET APART CONNECTED TO THE SUBPANEL WITH A CONTINUOUS #4 GROUND WIRE - DO NOT POWER SUBPANEL, YOU MUST PROTECT MMC CABLE BELOW 8 FEET, INSTALL COVERS ON ALL ELEC OUTLETS
11/25/1997 ELECTRIC - INTERMEDIATE Partial Approval