Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T97CM00977

Inspection Status: Correction Required

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
11/25/1997 ELECTRIC - UNDERGROUND Correction Required ADDTL COMMS - OK TO COVER UNDERGROUND - YOU MUST INSTALL 2 GROUND RODS 8 LONG INSTALLED 6 FEET APART