Inspection Status: Correction Required
Inspection History: BUILDING PRE-SLAB
| Date |
Description |
Inspector |
Results |
Comments |
| 11/26/1997 |
BUILDING PRE-SLAB |
|
Correction Required |
ADDTL COMMS - PLEASE HAVE AS BUILTSAPP. @PORCH HIP ROOF AREA OK TO POUR BY PLANS CHECKER. |
| 09/09/1997 |
BUILDING PRE-SLAB |
|
Partial Approval |
LAUNDRY & PORCHES OK |
| 08/15/1997 |
BUILDING PRE-SLAB |
|
Partial Approval |
UNIT B OK TO POUR |
| 08/14/1997 |
BUILDING PRE-SLAB |
|
Correction Required |
ADDTL COMMS - 1. SEE 13/A3 CALLS FOR 1-#5 REBAR @ 48 O.C.--#4 USED. HAVR PLANS REVISED & AAP. BY C.O.T. 2. FOUNDATION PLAN ON A-Z CALLS FOR FOOTINGS TO BE 24X24 BUT DETAIL 4/A3 CALLS FOR 18X24. 3. EAST FOOTING DOES NOT MEET SIZE OF EITHER ABOVE MENTIONED. |
| 08/14/1997 |
BUILDING PRE-SLAB |
|
Not ready for Inspection |
SEE NOTES |
| 08/14/1997 |
BUILDING PRE-SLAB |
|
Denied |
DENIED |