Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/24/2007 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 08/23/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 09/11/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. NO ONE HOME--NO ACCESS TO PROPERTY 2. DOGS MUST BE LOCKED UP. 3. YOU MUST POST "520" ADDRESS ON HOUE VISABLE. 4. ELECTRIC SERVICE PANEL FAMILY ROOM LIGHTS AND RECEPTACLES WIRED WITH 14 GA WIRE MUST BE ON 15 AMP BREAKERS. 5. ELECTRIC OUTLET MISSING COVER. 6. WATER HEATER "B" VENT MUST HAVE 1" TO COMBUSTABLES AND ALSO MUST EXTEND 1" BELOW DRYWALL CEILING. 7. W/H GAS FEX CANNOT EXCEED 3 FT. IN LENGTH. 8. JACCUZI MUST HAVE ACCESS PANEL TO PUMP BATHROOM NOT COMPLETE. 9. ALL BEDROOMS MUST HAVE BATTERY OPERATED SMOKE/DETECTOR. NOTE: WE WORK FROM 0630 AM TO 3100 PM AND INSPECT FROM 0700 AM TO 245 PM YOU MUST BE AVAILABLE OR PROVIDE A PHONE NUMBER FOR US TO CALL YOU TO BE AVAILABLE BETWEEN THOSE HOURS. |