Permit: T97CM00216

Parcel: 11517123A


Addresses:

1818 N DRAGOON ST


Inspection Status: Not ready for Inspection

Inspection History: FRAMING

Permit Number - T97CM00216

Inspection Description - FRAMING

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
04/08/2014 FRAMING Not ready for Inspection INSPECTION NOT PERFORMED. OWNER STATED THAT THEY ARE PUTTING THE HOUSE UP FOR SALE AS IS.
05/24/2013 FRAMING Not ready for Inspection IVRS - Inspection :*
05/24/2013 FRAMING Not ready for Inspection NEED PLUMBING INTERMEDIATE
FRAME, MECH, & ELECT OK
OK TO INSULATE EXCEPT PLUMB
11/03/2011 FRAMING Partial Approval IVRS - Inspection :*
1) RE-DO DRYER VENT, PLENIUM AREA AND WASHER BOX UP
05/10/2011 FRAMING Not ready for Inspection IVRS - Inspection :*
11/15/2010 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE ROMEX 8" FROM BOXES
2) NAIL PROTECT PLUMBING THROUGHOUT
3) CRIPPLES KITCHE DOOR
4) SECURE 4 GANG BOXES
5) 4" DRYER VENT REQUIRED RIGID
6) NAIL PROTECT TPR LINE
7) OVERSPAN TO MAST BATH
8) PROVIDE 1/2" CLEARANCE FOR DEFLECTION 2 PT BEARING TRUSSES
9) CHECK ALL DUCT INSULATION
10) CHECK ALL HEADERS NAILING
11) PROVIDE GAS AND WATER BONDS
12) PROVIDE TEST ABS AND POTABLE
06/01/2010 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CLEAN ALL DEBRIS FROM HERE FOR INSPECTION
2) REMOVE ALL PLYWOOD FROM WINDOWS FOR INSPECTION
3) ALL TRADES TO BE REINSPECTED DUE TO ?
01/31/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
1) DUE TO VANDALISM
07/11/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DENIED-COMPLETE ALL AND RECALL
2) SEE PREVIOUS SHEET DATED 4/6/05
10/04/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/30/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOCKED-UNABLE TO MAKE INSPECTION
04/06/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FRONT AND REAR PORCH CALLS FOR 6" X 10" BEAM .
2) INSTALL KITCHEN SINK CLEANOUT
3) H20 HEATER ROOM WALL NOT FRAMED IN
4) EXTEND FIRE PIPES INTO CEILING ? ROOM
5) GROUND ALL METAL ELECTRIC BOXES
6) MAKE UP ALL GROUNDS ELECTRIC BOXES
7) MAINTAIN 1" CLEARANCE FLUE PIPES TO COMBUSTIBLES AND SECURE IN PLACE
8) BOX IN AROUND KITCHEN EXHAUST DUCT
9) EXTEND MECHANICAL DUCTS THROUGH CEILING MECH ROOM
10) INSTALL BANG PLATE PROTECTION ALL PLUMBING AND ELECTRIC HOLES THROUGH STUDS
11) NEED H20 TEST DWV SYSTEM AND POTABLE H20 SUPPLY
12) INSTALL JOIST HANGER ALL 2 X TRUSS MEMBERS TO GIRDERS AND HIPS
13) NEED ENGINEERED TRUSS REPAIR WHERE GAS LINE GOES THROUGH BOTTOM CHORD
14) SUPPLY APPROVED HANGER BEDROOM GIRDER ATTACHMENT
15) INSTALL APPROVED CONNECTIONS MASONRY TO FRAME CONNECTIONS
16) NEED VERIFICATION OF 01015, 01020
17) NEED APPROVED TRUSS DRAWINGS
18) MUST USE 10D NAILS ? JOIST HANGERS
19) MUST USE TECO NAILS IN HURRICANE TIES
20) STOPPED INSPECTION
21) COMPLETE AND RECALL
10/26/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) LOCKED HOUSE. NO ACCESS
11/18/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*
12/17/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) COMPLETE ALL TRADES PRIOR TO FRAME INSPECTION