Permit: T97BU02271

Parcel: 141141680

Inspection Status: Correction Required

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
12/12/1997 POOL/SPA ELECTRIC Correction Required ADDTL COMMS - 1. INSTALL WIRE PROTECTOR BUSHING AT SPA CONTROL BOX. 2. FLEX NON METALIC CONDUIT CAN NOT RUN UNDERGROUND. 3. INPROPER SPLICE ON NEUTRAL WIRE TO SPA. 4. YOU MUST HAVE SEPARATE ISOLATED NEUTRAL ADN GROUND BARS AT SUB PANEL.
12/12/1997 POOL/SPA ELECTRIC Denied DENIED
12/04/1997 POOL/SPA ELECTRIC Correction Required ADDTL COMMS - POOL ELEC CONNECTED TO AN UNSAFE ELEC SUB PANEL. DISCONNECT FROM THIS PANEL ALL POOL CIRCUITS. OK TO GUNITE.
12/04/1997 POOL/SPA ELECTRIC Partial Approval PARTIAL APPROVAL